Skip to content

Lifebreath 1500E-ECM Large Commercial Heat Recovery Ventilator (HRV)

Model: 1500E-ECM

Airflow's up to 1500 CFM; This high efficient, 3 speed unit features brush less DC motors producing quiet, long lasting operation while reducing energy cost. Standard fan defrost and various duct configurations available.

Warranty: Units carry a 15 year warranty on the HRV core and a 2 year replacement parts warranty.
  • 6x Cross Flow Cores
  • Outdoor rooftop installation. Fresh Air to building and Stale Air from building connections are underneath unit.
  • High Efficiency ECM motor
  • Microprocessor circuit board with built in interlock contacts.

Voltage 240 V
Frequency 60 Hz
Phase 1
Current 18 A
Airflow High 1550 CFM
Static Pressure 0 IN. WG
Weight 240 lb
Drain Yes
Motors and Blowers ECM 1 HP motors (variable speed, double shafted) and one forward curved blower on each stream.
Core The cross flow heat exchanger balances efficiency, compact size and excellent cold temperature performance. With our recirculation defrost strategy the sensible heat recovery efficiency (SRE) at -25C (defrosting) can be within a few percent of the 0C SRE (no defrost) delivering significant energy savings. Each core is tested to ensure low leakage.
Defrost Fan
Serviceability Slide in and out core and filter. Service clearance 30 in.
Case 20GA Powder Coat steel exterior.
Insulation 1" Elastomeric
Filters 2 Filters, MERV 6, 20"x16"x2" Ea. Stream
Mounting Unit to be set on support brackets hung by threaded rod type apparatus (brackets and rods not provided).